080Z2811 - Danfoss Gas Detecting Sensor, DGS gr. 3
The Danfoss 080Z2811 gas sensor is designed for use with the AKM4 system and is compatible with refrigerant R407C. It uses a semiconductor sensor to detect HFC leaks in the 0–2000 ppm range. Built-in LED and buzzer provide local alerts. The sensor supports both 21–27 V AC and 19–29 V DC input and includes cable glands and a calibration certificate.
Product Specifications:
- Sensor type: Semiconductor
- Detection range: 0–2000 ppm
- Alarm limits: 500 ppm (low and high)
- Compatible refrigerant: R407C
- Used with: AKM4
- Supply voltage (AC): 21–27 V
- Supply voltage (DC): 19–29 V
- Power consumption: 0.25 A
- Frequency: 50/60 Hz
- Temperature range: -35°C to 60°C (-31°F to 140°F)
- Relative humidity: 15%–90%
- Response delay: 0 seconds
- Function: USB Hasp for AKM4
- Includes: Cable glands, calibration certificate
- Type: DGS
- Type designation: AKM
- Gross weight: 0.37 kg
- Net weight: 0.25 kg
- Product group: Sensors